Type | Items | Specification |
Capacity | Capacity | 2000VA/1400W |
Input | Voltage Range | 220 +/- 25% VAC |
| Frequency Range | 50 +/- 10% Hz |
| Phase | Single Phase with Ground |
| Current THDI | <12% |
| Power Factor | 0.98 |
| Generator Input | Support |
Output | Voltage Range | 220 +/- 1% VAC |
| Frequency Range | 50 +/- 0.1% Hz |
| Crest Factor | 3:1 |
| Harmonic Distortion | <= 3% THD (Linear Load) |
| Output Wave form | Pure Sine Wave |
| Outlet | NEMA |
| Overload Capacity | 60s @ 100%-130%; 1s @ >130% |
| Redundancy (Option) | Dual Modular Redundant (DMR) |
Efficiency | AC mode | 86% |
Battery | Number of Battery | 4 pcs. or on requested |
| Battery type | 12V/7A (Sealed Lead-Acid Maintenance Free with suspended electrolyte) or on requested |
| Backup time | >15 min (Depend on computer load) |
| Recharge Time (to 90%) | 5 hrs. |
Transfer Time | Transfer Time | 0 ms. |
Indicator | LED version (Option) | Load Level/Battery Level/Battery Mode/AC Mode/Bypass Mode/Fault |
| LCD version | Load/Battery/Input/Output/Operation Mode Information |
Audible Alarm | Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously Sounding |
Dimension | Tower Case (DxWxH)mm | 369x190x318 |
Weight | Tower Case (kgs) | 20 |
Environment | Operation Environment | 0-40 C |
| Relative Humidity | 0-90% (Non-Condensing) |
| Noise Level | <45dB @ 1 Meter |
Interface | Smart RS-232 / USB (Option) | S/W supports Windows Family, Linux, Sun Solaris, IBM AIX, Compaq True64, SGI IRIX, FreeBSD, HP-UX and MAC |
| External Slot (Option) | External Type of SNMP / AS400 Relay Card / RS485 |
International Standard | CE | Low Voltage Directive(Safety): EN62040-1-1,
EMC Directive: EN62040-2, EN61000-2-2, EN61000-4-2,
EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6,
EN61000-4-8, EN61000-3-2, EN61000-3-3 |